-67-
11. OTHER PROGRAMMING
11.6 Alarm Deadband
A deadband can be programmed between alarm-activation and alarm-reset.
Press and simultaneously in the operation screen for 3 seconds or more to display the [Alarm
deadband] programming screen. This programming is common to all alarm points.
1 Alarm Deadband
An alarm activates when a measured value
exceeds the alarm value. The alarm reset is
executed at a value that is lower than the
alarm value. This difference is called the
deadband and is specified with a scale width
(%).
The programming range is 0.1 to 9.9% and
can be programmed in 0.1% increments.
The default is 0.1%.
Low alarm
High alarm
2 Programming Flow Chart
<Example> From 0.1% to 0.5%
Operation screen
[Check]



[To be ready for programming]



[Programming deadband]



Stored
Dead
band
Dead
band
ON
ON
OFF
OFF
(Reset) (Reset)
MIN MAX
MAX
MIN
(Activation
)
A
larm value
A
larm value
Alarm deadband
3 sec. or
more
Decimal point is fixed.
Cursor
Deadband
SHIFT
°
C
DISP
SHIFT
SET
END
°
F
5
DATA I
ENTRY
°
C
(Activation)